Weschler Instruments – Manufacturer & distributor of measurement & control equipment
440.238.2550   /   800.557.0064   /   
analog meters, digital meters, transducers, signal conditioners, data loggers and test instrumentation
Home | About Us | What's New | Industries | Weschler Products | All Products | Meter Mod Center | Reference | Contact | Site
Search Catalog 
      GO   
 All Categories    CUB5 Digital Panel Meters - Red Lion
Weschler Instruments is a manufacturer and distributor of electrical and electronic measurement equipment. Customers worldwide use our products in power plants, steel mills, chemical plants, paper mills and other industrial applications that require rugged, reliable and accurate instrumentation.
All Categories > Digital Meters > Red Lion Digital Panel Meters > CUB5 Digital Panel Meters - Red Lion > View Items 
    Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites

CUB5 Digital Panel Meters - Red Lion

Check up to five results to perform an action.

CUB5I Digital Panel Meters

larger image
  • Voltage, Current, Process & Temperature Inputs
  • Five Digit 0.48" (12 mm) LCD
  • Red/Green Backlight Changes at Setpoint
  • Input Scaling & Units Annunciator
  • Min / Max Display Capture
  • NEMA 4X/IP65 Front
  • Setpoint Relay Output Options
  • Optional RS232, RS485 or USB Communications
  • Crimson Software for Simple Programming
  • CE Approved, C-UL Listed
The CUB5I offers 4 DC current ranges with a maximum input of 200 mA. The CUB5V has 4 DC voltage ranges and a maximum input of 200 VDC.
  • Current Ranges: 0 to 199.99 uA, 1.9999 mA, 19.999 mA, 199.99 mA
  • Voltage Ranges: 0 to 199.99 mV, 1.9999 V, 19.999 V, 199.99 V
The CUB5P accepts signals from flow meters, pressure sensors, position sensors and other process transmitters. Display can be scaled for readout in the desired units.
  • Ranges: 4 to 20 mA, 10 to 50 mA, 0 to 10 V
  • Span and Offset Capability
For temperature measurements, the CUB5RT accepts inputs from several types of RTD sensors. The CUB5TC accepts all popular thermocouples.
  • RTD: Pt385, Pt392, Ni672, Cu427
  • Thermocouple: T, E, J, K, R, S, B, N, or mV
The capability of the CUB5 can be easily expanded with plug-in option cards. Setpoint capability is field installable with the addition of a setpoint output card. Serial communications capability for RS232, RS485 or USB is added with a serial option card. The CUB5 can be powered from an optional Red Lion Micro Line /Sensor Power Supply (MLPS), which attaches directly to the back of a CUB5. The MLPS operates from 85 to 250 VAC and provides up to 400 mA to drive the meter and sensors.




Request InformationCompare Items   Results Per Page : 
  Results 1 - 20 of 20 1 

Item #

Item Name

Options Factory Installed

Range

Input

CUB5IR00 DC Current Meter with Reflective Display No 2 mADC, Resolution: 0.1 µA, Input R: 111 ohm, Max. Input: 50 mA
20 mADC, Resolution: 1 µA, Input R: 11 ohm, Max. Input: 150 mA
200 µADC, Resolution: 10 nA, Input R: 1.111 kohm, Max. Input: 15 mA
200 mADC, Resolution: 10 µA, Input R: 1 ohm, Max. Input: 500 mA
N/A
CUB5IB00 DC Current Meter with Backlight Display No 2 mADC, Resolution: 0.1 µA, Input R: 111 ohm, Max. Input: 50 mA
20 mADC, Resolution: 1 µA, Input R: 11 ohm, Max. Input: 150 mA
200 µADC, Resolution: 10 nA, Input R: 1.111 kohm, Max. Input: 15 mA
200 mADC, Resolution: 10 µA, Input R: 1 ohm, Max. Input: 500 mA
N/A
CUB5VR00 DC Volt Meter with Reflective Display No 2 VDC, Resolution: 0.1 mV, Input R: 1.027 Mohm, Max. Input: 75 VDC
20 VDC, Resolution: 1 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
200 mVDC, Resolution: 10 µV, Input R: 1.027 Mohm, Max. Input: 75 VDC
200 VDC, Resolution: 10 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
N/A
CUB5VB00 DC Volt Meter with Backlight Display No 2 VDC, Resolution: 0.1 mV, Input R: 1.027 Mohm, Max. Input: 75 VDC
20 VDC, Resolution: 1 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
200 mVDC, Resolution: 10 µV, Input R: 1.027 Mohm, Max. Input: 75 VDC
200 VDC, Resolution: 10 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
N/A
CUB5PR00 Process Meter with Reflective Display No 10 VDC, Resolution: 1 mV, Input R: 538 kohm, Max. Input: 30 V
20 / 50 mADC, Resolution: 1 µA, Input R: 10 ohm, Max. Input: 150 mA
N/A
CUB5PB00 Process Meter with Backlight Display No 10 VDC, Resolution: 1 mV, Input R: 538 kohm, Max. Input: 30 V
20 / 50 mADC, Resolution: 1 µA, Input R: 10 ohm, Max. Input: 150 mA
N/A
CUB5TCR0 Thermocouple Meter with Reflective Display No mV, Range: -10.00 to 65.00, Accuracy 23°C: 0.02 mV, Accuracy 0-50°C: 0.08 mV
TC Type B, Range: 200 to 540°C, Accuracy 23°C: 9.1°C, Accuracy 0-50°C: 42.6°C
TC Type B, Range: 540 to 1820°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type E, Range: -200 to 871°C, Accuracy 23°C: 2.7°C, Accuracy 0-50°C: 4.9°C
TC Type J, Range: -200 to 760°C, Accuracy 23°C: 1.9°C, Accuracy 0-50°C: 4.3°C
TC Type K, Range: -200 to 1372°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
TC Type N, Range: -200 to 1300°C, Accuracy 23°C: 2.8°C, Accuracy 0-50°C: 8.1°C
TC Type R, S, Range: -50 to 1768°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type T, Range: -200 to 400°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
ohm
CUB5TCB0 Thermocouple Meter with Backlight Display No mV, Range: -10.00 to 65.00, Accuracy 23°C: 0.02 mV, Accuracy 0-50°C: 0.08 mV
TC Type B, Range: 200 to 540°C, Accuracy 23°C: 9.1°C, Accuracy 0-50°C: 42.6°C
TC Type B, Range: 540 to 1820°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type E, Range: -200 to 871°C, Accuracy 23°C: 2.7°C, Accuracy 0-50°C: 4.9°C
TC Type J, Range: -200 to 760°C, Accuracy 23°C: 1.9°C, Accuracy 0-50°C: 4.3°C
TC Type K, Range: -200 to 1372°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
TC Type N, Range: -200 to 1300°C, Accuracy 23°C: 2.8°C, Accuracy 0-50°C: 8.1°C
TC Type R, S, Range: -50 to 1768°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type T, Range: -200 to 400°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
ohm
CUB5RTR0 RTD Meter with Reflective Display No 10 ohm Copper 427, Range: -100 to 260°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 0.9°C
100ohm Pt 385/392, Range: -200 to 850°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 1.6°C
120 ohm Nickel 672, Range: -80 to 260°C, Accy. 23°C: 0.2°C, Accy. 0-50°C: 0.5°C
2, 3 or 4 wire sensor, 10ohm max lead res. (3ohm on Cu RTD)
CUB5RTB0 RTD Meter with Backlight Display No 10 ohm Copper 427, Range: -100 to 260°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 0.9°C
100ohm Pt 385/392, Range: -200 to 850°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 1.6°C
120 ohm Nickel 672, Range: -80 to 260°C, Accy. 23°C: 0.2°C, Accy. 0-50°C: 0.5°C
2, 3 or 4 wire sensor, 10ohm max lead res. (3ohm on Cu RTD)
CUB5IR00-ASSY DC Current Meter with Reflective Display Yes 2 mADC, Resolution: 0.1 µA, Input R: 111 ohm, Max. Input: 50 mA
20 mADC, Resolution: 1 µA, Input R: 11 ohm, Max. Input: 150 mA
200 µADC, Resolution: 10 nA, Input R: 1.111 kohm, Max. Input: 15 mA
200 mADC, Resolution: 10 µA, Input R: 1 ohm, Max. Input: 500 mA
N/A
CUB5IB00-ASSY DC Current Meter with Backlight Display Yes 2 mADC, Resolution: 0.1 µA, Input R: 111 ohm, Max. Input: 50 mA
20 mADC, Resolution: 1 µA, Input R: 11 ohm, Max. Input: 150 mA
200 µADC, Resolution: 10 nA, Input R: 1.111 kohm, Max. Input: 15 mA
200 mADC, Resolution: 10 µA, Input R: 1 ohm, Max. Input: 500 mA
N/A
CUB5VR00-ASSY DC Volt Meter with Reflective Display Yes 2 VDC, Resolution: 0.1 mV, Input R: 1.027 Mohm, Max. Input: 75 VDC
20 VDC, Resolution: 1 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
200 mVDC, Resolution: 10 µV, Input R: 1.027 Mohm, Max. Input: 75 VDC
200 VDC, Resolution: 10 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
N/A
CUB5VB00-ASSY DC Volt Meter with Backlight Display Yes 2 VDC, Resolution: 0.1 mV, Input R: 1.027 Mohm, Max. Input: 75 VDC
20 VDC, Resolution: 1 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
200 mVDC, Resolution: 10 µV, Input R: 1.027 Mohm, Max. Input: 75 VDC
200 VDC, Resolution: 10 mV, Input R: 1.027 Mohm, Max. Input: 250 VDC
N/A
CUB5PR00-ASSY Process Meter with Reflective Display Yes 10 VDC, Resolution: 1 mV, Input R: 538 kohm, Max. Input: 30 V
20 / 50 mADC, Resolution: 1 µA, Input R: 10 ohm, Max. Input: 150 mA
N/A
CUB5PB00-ASSY Process Meter with Backlight Display Yes 10 VDC, Resolution: 1 mV, Input R: 538 kohm, Max. Input: 30 V
20 / 50 mADC, Resolution: 1 µA, Input R: 10 ohm, Max. Input: 150 mA
N/A
CUB5TCR0-ASSY Thermocouple Meter with Reflective Display Yes mV, Range: -10.00 to 65.00, Accuracy 23°C: 0.02 mV, Accuracy 0-50°C: 0.08 mV
TC Type B, Range: 200 to 540°C, Accuracy 23°C: 9.1°C, Accuracy 0-50°C: 42.6°C
TC Type B, Range: 540 to 1820°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type E, Range: -200 to 871°C, Accuracy 23°C: 2.7°C, Accuracy 0-50°C: 4.9°C
TC Type J, Range: -200 to 760°C, Accuracy 23°C: 1.9°C, Accuracy 0-50°C: 4.3°C
TC Type K, Range: -200 to 1372°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
TC Type N, Range: -200 to 1300°C, Accuracy 23°C: 2.8°C, Accuracy 0-50°C: 8.1°C
TC Type R, S, Range: -50 to 1768°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type T, Range: -200 to 400°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
ohm
CUB5TCB0-ASSY Thermocouple Meter with Backlight Display Yes mV, Range: -10.00 to 65.00, Accuracy 23°C: 0.02 mV, Accuracy 0-50°C: 0.08 mV
TC Type B, Range: 200 to 540°C, Accuracy 23°C: 9.1°C, Accuracy 0-50°C: 42.6°C
TC Type B, Range: 540 to 1820°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type E, Range: -200 to 871°C, Accuracy 23°C: 2.7°C, Accuracy 0-50°C: 4.9°C
TC Type J, Range: -200 to 760°C, Accuracy 23°C: 1.9°C, Accuracy 0-50°C: 4.3°C
TC Type K, Range: -200 to 1372°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
TC Type N, Range: -200 to 1300°C, Accuracy 23°C: 2.8°C, Accuracy 0-50°C: 8.1°C
TC Type R, S, Range: -50 to 1768°C, Accuracy 23°C: 4.5°C, Accuracy 0-50°C: 15.0°C
TC Type T, Range: -200 to 400°C, Accuracy 23°C: 2.3°C, Accuracy 0-50°C: 5.8°C
ohm
CUB5RTR0-ASSY RTD Meter with Reflective Display Yes 10 ohm Copper 427, Range: -100 to 260°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 0.9°C
100ohm Pt 385/392, Range: -200 to 850°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 1.6°C
120 ohm Nickel 672, Range: -80 to 260°C, Accy. 23°C: 0.2°C, Accy. 0-50°C: 0.5°C
2, 3 or 4 wire sensor, 10ohm max lead res. (3ohm on Cu RTD)
CUB5RTB0-ASSY RTD Meter with Backlight Display Yes 10 ohm Copper 427, Range: -100 to 260°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 0.9°C
100ohm Pt 385/392, Range: -200 to 850°C, Accy. 23°C: 0.4°C, Accy. 0-50°C: 1.6°C
120 ohm Nickel 672, Range: -80 to 260°C, Accy. 23°C: 0.2°C, Accy. 0-50°C: 0.5°C
2, 3 or 4 wire sensor, 10ohm max lead res. (3ohm on Cu RTD)
  Results 1 - 20 of 20 1